| General specifications | 
		
			| Switching function | Normally closed (NC) | 
		
			| Output type | NAMUR | 
		
			| Rated operating distance | 10 mm | 
		
			| Installation | flush | 
		
			| Assured operating distance | 0 ... 8.1 mm | 
		
			| Actual operating distance | 9 ... 11 mm typ. | 
		
			| Reduction factor rAl | 0.35 | 
		
			| Reduction factor rCu | 0.3 | 
		
			| Reduction factor r304 | 0.75 | 
		
			| Output type | 2-wire | 
		
			| Nominal ratings | 
		
			| Nominal voltage | 8.2 V (Ri approx. 1 kΩ) | 
		
			| Switching frequency | 0 ... 200 Hz | 
		
			| Hysteresis | 1 ... 15 typ. 5 % | 
		
			| Reverse polarity protection | reverse polarity protected | 
		
			| Short-circuit protection | yes | 
		
			| Current consumption |  | 
		
			|  | Measuring plate not detected | min. 2.2 mA | 
		
			|  | Measuring plate detected | ≤ 1 mA | 
		
			| Switching state indicator | Multihole-LED, yellow | 
		
			| Functional safety related parameters | 
		
			| Safety Integrity Level (SIL) | SIL 2 | 
		
			| MTTFd | 1821 a | 
		
			| Mission Time (TM) | 20 a | 
		
			| Diagnostic Coverage (DC) | 0 % | 
		
			| Compliance with standards and directives | 
		
			| Standard conformity |  | 
		
			|  | NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999
 | 
		
			|  | Electromagnetic compatibility | NE 21:2007 | 
		
			|  | Standards | EN IEC 60947-5-2 | 
		
			| Approvals and certificates | 
		
			| IECEx approval |  | 
		
			|  | Equipment protection level Ga | IECEx PTB 11.0037X | 
		
			|  | Equipment protection level Gb | IECEx PTB 11.0037X | 
		
			|  | Equipment protection level Da | IECEx PTB 11.0037X | 
		
			|  | Equipment protection level Mb | IECEx PTB 11.0037X | 
		
			| ATEX approval |  | 
		
			|  | Equipment protection level Ga | PTB 00 ATEX 2048 X | 
		
			|  | Equipment protection level Gb | PTB 00 ATEX 2048 X | 
		
			|  | Equipment protection level Da | PTB 00 ATEX 2048 X | 
		
			| UL approval |  | 
		
			|  | Ordinary Location | E87056 | 
		
			|  | Hazardous Location | E501628 | 
		
			|  | Control drawing | 116-0452 | 
		
			| CCC approval |  | 
		
			|  | Hazardous Location | 2020322315002255 | 
		
			| NEPSI approval |  | 
		
			|  | NEPSI certificate | GYJ16.1393X | 
		
			| CML approval | on request | 
		
			| ANZEx | 18.3018X | 
		
			| KCC approval |  | 
		
			|  | Hazardous Location | 09-AV4BO-0226 | 
		
			| Marine approval | DNVGL TAA00001A5 | 
		
			| Ambient conditions | 
		
			| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) | 
		
			| Storage temperature | -40 ... 100 °C (-40 ... 212 °F) | 
		
			| Mechanical specifications | 
		
			| Connection type | Connector plug | 
		
			| Housing material | Stainless steel 1.4305 / AISI 303 | 
		
			| Sensing face | PBT | 
		
			| Degree of protection | IP67 | 
		
			| Connector |  | 
		
			|  | Threading | M12 x 1 | 
		
			|  | Number of pins | 4 | 
		
			| Dimensions |  | 
		
			|  | Length | 55 mm | 
		
			|  | Diameter | 30 mm | 
		
			| General information | 
		
			| Use in the hazardous area | see instruction manuals |